ITEM 1 : INSULATION COVER FOR 70 MM2 - 15 KV | ||||
ITEM | SPECIFICATIONS | UNIT | REQUIRED | GUARANTEED |
1 | GENERAL DATA | |||
1.1 | MANUFACTURER | INDICATE | HEMG | |
COUNTRY | INDICATE | China | ||
1.2 | MATERIAL OF INSULATION COVER | SILICON RUBBER | SILICONE RUBBER | |
1.3 | MODEL OR CATALOGUE NUMBER | INDICATE | WSKG | |
1.4 | CERTIFICATE ISO 9001 AND ISO 14001 | YES | YES | |
1.5 | STANDARDS OF MANUFACTURE AND TESTS | ACCORDING POINT 2 | ||
2 | CONDITIONS OF OPERATION IN CONTINUOUS REGIME OF THE INSULATING COVERS. | |||
2.1 | MAXIMUM VOLTAGE. | KV | 15 | 15 |
2.3 | NOMINAL VOLTAGES OF THE NETWORK. | KV | 10, 13.2, 13.8 | 10, 13.2, 13.8 |
2.4 | FREQUENCY | HZ | 60 | 60 |
2.5 | CALIBER OF CABLES WHERE THEY WILL BE INSTALLED. | UNTIL 70 MM2 | UNTIL 70 MM2 | |
2.6 | MATERIAL OF THE CABLES WHERE THEY WILL BE INSTALLED. | CU AND AAAC | CU AND AL | |
3 | ELECTRICAL PROPERTIES OF THE COVER MATERIAL (1). | |||
3.1 | DIELECTRIC STRENGTH. | KV/CM | 175 OR MORE | ≥175 |
3.2 | VOLUMETRIC RESISTIVITY. | OHM/CM | 1X10 13 OR MORE | 1X10 14 |
3.3 | CONSTANT DIELECTRIC. | 5 OR LESS | 2-3 | |
4 | VOLTAGES OF PROOF OF THE COVER (1). | |||
4.1 | A NOMINAL FREQUENCY IN DRY 1 MINUTE. | KV | 15 | 15 |
4.2 | A INDUSTRIAL FREQUENCY IN WET 1 MINUTE. | KV | 15 | 15 |
5 | PROPERTIES OF THE MATERIAL OF THE INSULATING COVER (1). | |||
5.1 | BREAKING STRAIN. | Mpa | 4.8 OR MORE | 4 |
5.2 | ELONGATION OF BREAK. | % | 200 OR MORE | ≥200 |
5.3 | RANGE OF OPERATING TEMPERATURE. | °C | FROM -10 TO +100 | from -10C to +100C |
5.4 | WATER ABSORPTION. | % | 1 OR LESS | 1 or less |
5.5 | RESISTANCE TO UV RAYS. | YES | yes | |
5.6 | RESISTANT TO TRACKING | YES | yes | |
5.7 | RESSITANTE TO THE MOZONO. | YES | yes | |
5.8 | RESISTANT TO URIC ACID AND FATS. | YES | yes | |
5.9 | RESISTANT TO THE RIPPED. | YES | yes | |
6 | DIMENSIONS AND DESIGN OF THE COVERS (2). | |||
6.1 | COVER DESIGN | INDICATE ADN SCHEME | ||
6.2 | THICKNESS. | mm | INDICATE. | ≥2.3 |
6.3 | INSIDE DIAMETER. | mm | INDICATE | 12 |
6.4 | CABLE CALIBERS TO COVER. | mm2 | INDICATE | 70 |
6.5 | LABELED. | BRAND AND MODEL | No | |
7 | INSTALLATION OF COVER WITH ENERGIZED LINE AND ITS ACCESSORIES (3). | |||
7.1 | EASY TO INSTALL. | YES , INCLUDE GUIDE | YES , INCLUDE GUIDE Pay attention to the personal safety with energized line | |
7.2 | INCLUDE RETAIN ACCESSORIES FOR FIXING THE CABLES AND AVOIDING SLIDES AFTER INSTALLATION. | YES, TWO UNITS FOR EVERY 10 MTS OF COVER. | CABLE TIE | |
7.3 | INCLUDE TOOLS FOR INSTALLATION AND CLOSURE OF THE COVER THAT GUARANTEE THAT DURING ITS OPERATION IS SLIDING ON THE CABLE AND PERIMETER ITS MOUNTING FROM A FIXED POINT OF THE INSTALLER WITH THE SPECIFIED TOOL. | YES, 5 EQUIPMENTS FOR MOUNTING | YES | |
7.4 | REUSABLE. | YES | YES, IF REQUIRED, WITHOUT GLUE | |
8 | PACKING REQUIREMENTS. | |||
8.1 | METERS OF COVER BY ROLL. | MTS | INDICATE | 100 |
8.2 | WEIGHT OF EACH ROLL. | KG | INDICATE | 10 |
8.3 | PACKAGING RESISTANT TO BLOWS AND FALL OF ACIDS. | INDICATE | YES | |
9 | PRESENT SAMPLE OF THE COVER AND FIXING ACCESSORIES. | YES, COVER AND ACCESORIE FOR MOUNTING. | YES | |
NOTE : | ||||
THE PROPERTIES OF THE INSULATING COVERS ARE REFERRED TO THE MANUFACTURING STANDARDS INDICATED IN THE NUMBER 2 attached. | ||||
IT MUST INCLUDE ROOF DESIGN DESIGNS INDICATING ALL DIMENSIONS, PLANS OF ACCESSORIES, FLATS OF FIXING ELEMENTS AND CLOSURE OF INSULATING COVERS. | ||||
THE FOLLOWING TECHNICAL DOCUMENTATION MUST BE INCLUDED. | ||||
Installation manuals, information on the technical characteristics of the fixing accessories, closure of the insulating covers and manuals for the use of the tools. | ||||
ITEM 2 : INSULATION COVER FOR 70 MM2 - 25 KV | ||||
ITEM | SPECIFICATIONS | UNIT | REQUIRED | GUARANTEED |
1 | GENERAL DATA | |||
1.1 | MANUFACTURER | INDICATE | HEMG | |
COUNTRY | INDICATE | China | ||
1.2 | MATERIAL OF INSULATION COVER | SILICON RUBBER | SILICONE RUBBER | |
1.3 | MODEL OR CATALOGUE NUMBER | INDICATE | WSKG | |
1.4 | CERTIFICATE ISO 9001 AND ISO 14001 | YES | YES | |
1.5 | STANDARDS OF MANUFACTURE AND TESTS | ACCORDING POINT 2 | ||
2 | CONDITIONS OF OPERATION IN CONTINUOUS REGIME OF THE INSULATING COVERS. | |||
2.1 | MAXIMUM VOLTAGE. | KV | 25 | 25 |
2.3 | NOMINAL VOLTAGES OF THE NETWORK. | KV | 22.9 | 22.9 |
2.4 | FREQUENCY | HZ | 60 | 60 |
2.5 | CALIBER OF CABLES WHERE THEY WILL BE INSTALLED. | UNTIL 70 MM2 | UNTIL 70 MM2 | |
2.6 | MATERIAL OF THE CABLES WHERE THEY WILL BE INSTALLED. | CU AND AAAC | CU AND AL | |
3 | ELECTRICAL PROPERTIES OF THE COVER MATERIAL (1). | |||
3.1 | DIELECTRIC STRENGTH. | KV/CM | 175 OR MORE | ≥175 |
3.2 | VOLUMETRIC RESISTIVITY. | OHM/CM | 1X10 13 OR MORE | 1X10 14 |
3.3 | CONSTANT DIELECTRIC. | 5 OR LESS | 2-3 | |
4 | VOLTAGES OF PROOF OF THE COVER (1). | |||
4.1 | A NOMINAL FREQUENCY IN DRY 1 MINUTE. | KV | 25 | 25 |
4.2 | A INDUSTRIAL FREQUENCY IN WET 1 MINUTE. | KV | 25 | 25 |
5 | PROPERTIES OF THE MATERIAL OF THE INSULATING COVER (1). | |||
5.1 | BREAKING STRAIN. | Mpa | 4.8 OR MORE | 4 |
5.2 | ELONGATION OF BREAK. | % | 200 OR MORE | ≥200 |
5.3 | RANGE OF OPERATING TEMPERATURE. | °C | FROM -10 TO +100 | from -10C to +100C |
5.4 | WATER ABSORPTION. | % | 1 OR LESS | 1 or less |
5.5 | RESISTANCE TO UV RAYS. | YES | yes | |
5.6 | RESISTANT TO TRACKING | YES | yes | |
5.7 | RESSITANTE TO THE MOZONO. | YES | yes | |
5.8 | RESISTANT TO URIC ACID AND FATS. | YES | yes | |
5.9 | RESISTANT TO THE RIPPED. | YES | yes | |
6 | DIMENSIONS AND DESIGN OF THE COVERS (2). | |||
6.1 | COVER DESIGN | INDICATE ADN SCHEME | ||
6.2 | THICKNESS. | mm | INDICATE. | ≥3 |
6.3 | INSIDE DIAMETER. | mm | INDICATE | 12 |
6.4 | CABLE CALIBERS TO COVER. | mm2 | INDICATE | 70 |
6.5 | LABELED. | BRAND AND MODEL | No | |
7 | INSTALLATION OF COVER WITH ENERGIZED LINE AND ITS ACCESSORIES (3). | |||
7.1 | EASY TO INSTALL. | YES , INCLUDE GUIDE | YES , INCLUDE GUIDE Pay attention to the personal safety with energized line | |
7.2 | INCLUDE RETAIN ACCESSORIES FOR FIXING THE CABLES AND AVOIDING SLIDES AFTER INSTALLATION. | YES, TWO UNITS FOR EVERY 10 MTS OF COVER. | CABLE TIE | |
7.3 | INCLUDE TOOLS FOR INSTALLATION AND CLOSURE OF THE COVER THAT GUARANTEE THAT DURING ITS OPERATION IS SLIDING ON THE CABLE AND PERIMETER ITS MOUNTING FROM A FIXED POINT OF THE INSTALLER WITH THE SPECIFIED TOOL. | YES, 5 EQUIPMENTS FOR MOUNTING | YES, | |
7.4 | REUSABLE. | YES | YES, IF REQUIRED, WITHOUT GLUE | |
8 | PACKING REQUIREMENTS. | |||
8.1 | METERS OF COVER BY ROLL. | MTS | INDICATE | 100 |
8.2 | WEIGHT OF EACH ROLL. | KG | INDICATE | 10 |
8.3 | PACKAGING RESISTANT TO BLOWS AND FALL OF ACIDS. | INDICATE | YES | |
9 | PRESENT SAMPLE OF THE COVER AND FIXING ACCESSORIES. | YES, COVER AND ACCESORIE FOR MOUNTING. | YES | |
NOTE : | ||||
THE PROPERTIES OF THE INSULATING COVERS ARE REFERRED TO THE MANUFACTURING STANDARDS INDICATED IN THE NUMBER 2 attached. | ||||
IT MUST INCLUDE ROOF DESIGN DESIGNS INDICATING ALL DIMENSIONS, PLANS OF ACCESSORIES, FLATS OF FIXING ELEMENTS AND CLOSURE OF INSULATING COVERS. | ||||
THE FOLLOWING TECHNICAL DOCUMENTATION MUST BE INCLUDED. | ||||
Installation manuals, information on the technical characteristics of the fixing accessories, closure of the insulating covers and manuals for the use of the tools. | ||||
ITEM 3 : INSULATION COVER FOR 120 MM2 - 15 KV | ||||
ITEM | SPECIFICATIONS | UNIT | REQUIRED | GUARANTEED |
1 | GENERAL DATA | |||
1.1 | MANUFACTURER | INDICATE | HEMG | |
COUNTRY | INDICATE | China | ||
1.2 | MATERIAL OF INSULATION COVER | SILICON RUBBER | SILICONE RUBBER | |
1.3 | MODEL OR CATALOGUE NUMBER | INDICATE | WSKG | |
1.4 | CERTIFICATE ISO 9001 AND ISO 14001 | YES | YES | |
1.5 | STANDARDS OF MANUFACTURE AND TESTS | ACCORDING POINT 2 | YES | |
2 | CONDITIONS OF OPERATION IN CONTINUOUS REGIME OF THE INSULATING COVERS. | |||
2.1 | MAXIMUM VOLTAGE. | KV | 15 | 15 |
2.3 | NOMINAL VOLTAGES OF THE NETWORK. | KV | 10, 132, 13.8 | 10, 13.2, 13.8 |
2.4 | FREQUENCY | HZ | 60 | 60 |
2.5 | CALIBER OF CABLES WHERE THEY WILL BE INSTALLED. | UNTIL 120 MM2 | UNTIL 120 MM2 | |
2.6 | MATERIAL OF THE CABLES WHERE THEY WILL BE INSTALLED. | CU AND AAAC | CU AND AL | |
3 | ELECTRICAL PROPERTIES OF THE COVER MATERIAL (1). | |||
3.1 | DIELECTRIC STRENGTH. | KV/CM | 175 OR MORE | ≥175 |
3.2 | VOLUMETRIC RESISTIVITY. | OHM/CM | 1X10 13 OR MORE | 1X10 14 |
3.3 | CONSTANT DIELECTRIC. | 5 OR LESS | 2-3 | |
4 | VOLTAGES OF PROOF OF THE COVER (1). | |||
4.1 | A NOMINAL FREQUENCY IN DRY 1 MINUTE. | KV | 15 | 15 |
4.2 | A INDUSTRIAL FREQUENCY IN WET 1 MINUTE. | KV | 15 | 15 |
5 | PROPERTIES OF THE MATERIAL OF THE INSULATING COVER (1). | |||
5.1 | BREAKING STRAIN. | Mpa | 4.8 OR MORE | 4 |
5.2 | ELONGATION OF BREAK. | % | 200 OR MORE | ≥200 |
5.3 | RANGE OF OPERATING TEMPERATURE. | °C | FROM -10 TO +100 | from -10C to +100C |
5.4 | WATER ABSORPTION. | % | 1 OR LESS | 1 or less |
5.5 | RESISTANCE TO UV RAYS. | YES | yes | |
5.6 | RESISTANT TO TRACKING | YES | yes | |
5.7 | RESSITANTE TO THE MOZONO. | YES | yes | |
5.8 | RESISTANT TO URIC ACID AND FATS. | YES | yes | |
5.9 | RESISTANT TO THE RIPPED. | YES | yes | |
6 | DIMENSIONS AND DESIGN OF THE COVERS (2). | |||
6.1 | COVER DESIGN | INDICATE ADN SCHEME | ||
6.2 | THICKNESS. | mm | INDICATE. | ≥2.3 |
6.3 | INSIDE DIAMETER. | mm | INDICATE | 15.6 |
6.4 | CABLE CALIBERS TO COVER. | mm2 | INDICATE | 120 |
6.5 | LABELED. | BRAND AND MODEL | No | |
7 | INSTALLATION OF COVER WITH ENERGIZED LINE AND ITS ACCESSORIES (3). | |||
7.1 | EASY TO INSTALL. | YES , INCLUDE GUIDE | YES , INCLUDE GUIDE Pay attention to the personal safety with energized line | |
7.2 | INCLUDE RETAIN ACCESSORIES FOR FIXING THE CABLES AND AVOIDING SLIDES AFTER INSTALLATION. | YES, TWO UNITS FOR EVERY 10 MTS OF COVER. | CABLE TIE | |
7.3 | INCLUDE TOOLS FOR INSTALLATION AND CLOSURE OF THE COVER THAT GUARANTEE THAT DURING ITS OPERATION IS SLIDING ON THE CABLE AND PERIMETER ITS MOUNTING FROM A FIXED POINT OF THE INSTALLER WITH THE SPECIFIED TOOL. | YES, 5 EQUIPMENTS FOR MOUNTING | YES | |
7.4 | REUSABLE. | YES | YES, IF REQUIRED, WITHOUT GLUE | |
8 | PACKING REQUIREMENTS. | |||
8.1 | METERS OF COVER BY ROLL. | MTS | INDICATE | 100 |
8.2 | WEIGHT OF EACH ROLL. | KG | INDICATE | 10 |
8.3 | PACKAGING RESISTANT TO BLOWS AND FALL OF ACIDS. | INDICATE | YES | |
9 | PRESENT SAMPLE OF THE COVER AND FIXING ACCESSORIES. | YES, COVER AND ACCESORIE FOR MOUNTING. | YES | |
NOTE : | ||||
THE PROPERTIES OF THE INSULATING COVERS ARE REFERRED TO THE MANUFACTURING STANDARDS INDICATED IN THE NUMBER 2 attached. | ||||
IT MUST INCLUDE ROOF DESIGN DESIGNS INDICATING ALL DIMENSIONS, PLANS OF ACCESSORIES, FLATS OF FIXING ELEMENTS AND CLOSURE OF INSULATING COVERS. | ||||
THE FOLLOWING TECHNICAL DOCUMENTATION MUST BE INCLUDED. | ||||
Installation manuals, information on the technical characteristics of the fixing accessories, closure of the insulating covers and manuals for the use of the tools. | ||||
ITEM 4 : INSULATION COVER FOR 120 MM2 - 25 KV | ||||
ITEM | SPECIFICATIONS | UNIT | REQUIRED | GUARANTEED |
1 | GENERAL DATA | |||
1.1 | MANUFACTURER | INDICATE | HEMG | |
COUNTRY | INDICATE | China | ||
1.2 | MATERIAL OF INSULATION COVER | SILICON RUBBER | SILICONE RUBBER | |
1.3 | MODEL OR CATALOGUE NUMBER | INDICATE | WSKG | |
1.4 | CERTIFICATE ISO 9001 AND ISO 14001 | YES | YES | |
1.5 | STANDARDS OF MANUFACTURE AND TESTS | ACCORDING POINT 2 | ||
2 | CONDITIONS OF OPERATION IN CONTINUOUS REGIME OF THE INSULATING COVERS. | |||
2.1 | MAXIMUM VOLTAGE. | KV | 25 | 25 |
2.3 | NOMINAL VOLTAGES OF THE NETWORK. | KV | 22.9 | 22.9 |
2.4 | FREQUENCY | HZ | 60 | 60 |
2.5 | CALIBER OF CABLES WHERE THEY WILL BE INSTALLED. | UNTIL 120 MM2 | UNTIL 120 MM2 | |
2.6 | MATERIAL OF THE CABLES WHERE THEY WILL BE INSTALLED. | CU AND AAAC | CU AND AL | |
3 | ELECTRICAL PROPERTIES OF THE COVER MATERIAL (1). | |||
3.1 | DIELECTRIC STRENGTH. | KV/CM | 175 OR MORE | ≥175 |
3.2 | VOLUMETRIC RESISTIVITY. | OHM/CM | 1X10 13 OR MORE | 1X10 14 |
3.3 | CONSTANT DIELECTRIC. | 5 OR LESS | 2-3 | |
4 | VOLTAGES OF PROOF OF THE COVER (1). | |||
4.1 | A NOMINAL FREQUENCY IN DRY 1 MINUTE. | KV | 15 | 15 |
4.2 | A INDUSTRIAL FREQUENCY IN WET 1 MINUTE. | KV | 15 | 15 |
5 | PROPERTIES OF THE MATERIAL OF THE INSULATING COVER (1). | |||
5.1 | BREAKING STRAIN. | Mpa | 4.8 OR MORE | 4 |
5.2 | ELONGATION OF BREAK. | % | 200 OR MORE | ≥200 |
5.3 | RANGE OF OPERATING TEMPERATURE. | °C | FROM -10 TO +100 | from -10C to +100C |
5.4 | WATER ABSORPTION. | % | 1 OR LESS | 1 or less |
5.5 | RESISTANCE TO UV RAYS. | YES | yes | |
5.6 | RESISTANT TO TRACKING | YES | yes | |
5.7 | RESSITANTE TO THE MOZONO. | YES | yes | |
5.8 | RESISTANT TO URIC ACID AND FATS. | YES | yes | |
5.9 | RESISTANT TO THE RIPPED. | YES | yes | |
6 | DIMENSIONS AND DESIGN OF THE COVERS (2). | |||
6.1 | COVER DESIGN | INDICATE ADN SCHEME | ||
6.2 | THICKNESS. | mm | INDICATE. | ≥3 |
6.3 | INSIDE DIAMETER. | mm | INDICATE | 15.6 |
6.4 | CABLE CALIBERS TO COVER. | mm2 | INDICATE | 120 |
6.5 | LABELED. | BRAND AND MODEL | No | |
7 | INSTALLATION OF COVER WITH ENERGIZED LINE AND ITS ACCESSORIES (3). | |||
7.1 | EASY TO INSTALL. | YES , INCLUDE GUIDE | YES , INCLUDE GUIDE Pay attention to the personal safety with energized line | |
7.2 | INCLUDE RETAIN ACCESSORIES FOR FIXING THE CABLES AND AVOIDING SLIDES AFTER INSTALLATION. | YES, TWO UNITS FOR EVERY 10 MTS OF COVER. | CABLE TIE | |
7.3 | INCLUDE TOOLS FOR INSTALLATION AND CLOSURE OF THE COVER THAT GUARANTEE THAT DURING ITS OPERATION IS SLIDING ON THE CABLE AND PERIMETER ITS MOUNTING FROM A FIXED POINT OF THE INSTALLER WITH THE SPECIFIED TOOL. | YES, 5 EQUIPMENTS FOR MOUNTING | YES | |
7.4 | REUSABLE. | YES | YES, IF REQUIRED, WITHOUT GLUE | |
8 | PACKING REQUIREMENTS. | |||
8.1 | METERS OF COVER BY ROLL. | MTS | INDICATE | 100 |
8.2 | WEIGHT OF EACH ROLL. | KG | INDICATE | 10 |
8.3 | PACKAGING RESISTANT TO BLOWS AND FALL OF ACIDS. | INDICATE | YES | |
9 | PRESENT SAMPLE OF THE COVER AND FIXING ACCESSORIES. | YES, COVER AND ACCESORIE FOR MOUNTING. | YES | |
NOTE : | ||||
THE PROPERTIES OF THE INSULATING COVERS ARE REFERRED TO THE MANUFACTURING STANDARDS INDICATED IN THE NUMBER 2 attached. | ||||
IT MUST INCLUDE ROOF DESIGN DESIGNS INDICATING ALL DIMENSIONS, PLANS OF ACCESSORIES, FLATS OF FIXING ELEMENTS AND CLOSURE OF INSULATING COVERS. | ||||
THE FOLLOWING TECHNICAL DOCUMENTATION MUST BE INCLUDED. | ||||
Installation manuals, information on the technical characteristics of the fixing accessories, closure of the insulating covers and manuals for the use of the tools. |